Studi Kelayakan Sistem Pentanahan pada Gedung Teknik Elektro Universitas Andalas

  • Yudia Meka Seftiani Politeknik Negeri Padang
  • Novizon Novizon Universitas Andalas
Keywords: Grounding system, resistance

Abstract

The grounding system is one part of the electric power system that has an important role in flowing overcurrent from the electric power system to the ground due to electrical power system disturbances or lightning strikes that can endanger the building and its surroundings. This grounding system aims to protect humans, electrical equipment, and electrical installations from the danger of electrical short circuits. In compliance with official regulations, safety standards and according to general electrical installation regulatory standards (PUIL) to avoid the danger of lightning strikes in buildings, it is necessary to have grounding resistance value of less than five ohms and is made as small as possible. In this study, the measurement of grounding resistance seen from the depth of the grounding and the grounding resistance are arranged in parallel. The results of this study indicate that the  parallel grounding resistance method produces a more significant reduction in the value of  grounding resistance compared to the grounding resistance in a certain depth From the calculation results, the resistance value of the Electrical Engineering Building at Andalas University using a rod electrode with a diameter of 0.016 meters is 24.5 Ω with an electrode depth of 0.5 meters and at a depth of 1 meter a grounding value of 17.52 Ω is obtained. The deeper the depth of the electrode, the smaller the resulting resistance value, and installing a grounding system with the multirod method, namely arranging electrodes in parallel with a certain depth, obtains less resistance compared to not parallelizing the electrodes

Downloads

Download data is not yet available.

References

[1] Pronoto, A., Tumaliang, H., & Mangindaan, G. M. (2018). Analisa sistem pentanahan gardu induk teling dengan konstruksi grid. Pentanahan , 189-197.
[2] Wahyono, Budhi Prasetiyo, 2016. Analisa Pengaruh Jarak Dan Kedalaman Terhadap Nilai Tahanan Pembumian Dengan 2 Elektroda Batang,Prosiding SNST ke-4 Tahun 2016 Fakultas Teknik Universitas Wahid Hasyim Semarang.

[3] J. Fisika and U. N. Semarang, “Rancang Bangun Sistem Grounding Untuk,” pp. 115–124, 1998.
[4] Linda Pasaribu, Studi Analisis Pengaruh Jenis Tanah, Kelembaban, Temperatur dan Kadar Garam Terhadap Tahanan Pentanahan Tanah (Tesis). Universitas Indonesia, Jakarta, (2011).
[5] A. B. Pulungan, Sukardi, Ta’ali dan R. Miftahul, “Studi Kelayakan Sistem Grounding Pada Gedung Olahraga Universiras Negeri Padang,”Vol. 3, No.1, 2022, pp. 96 – 101, 2022
[6] Badan Standarisasi Nasional. 2000. Persyaratan Umum Instalasi Listrik 2000 (PUIL 2000). Jakarta: Yayasan PUIL
[7] Hutauruk, T.S. 1991. Pengetanahan Netral Sistem Tenaga Dan Pengetanahan Peralatan. Yayasan PUIL. Jakarta : Erlangga
[8] Tadjuddin. Bentuk - bentuk elektroda pentanahan. Elektro Indonesia Edisi ke Lima Belas, Nopember 2010
[9] Pabla, AS, Sistem Distribusi Daya Listrik, Erlangga: Jakarta, 1994
[10] Managam Rajagukguk, Studi Pengaruh Jenis Tanah dan Kedalaman Pembumian Driven Rod terhadap Resistansi Jenis Tanah, Universitas Tanjungpura, Pontianak, (2012).
[11] IEEE Std 142-2007. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems,(2007).
[12] N. Nurdiana and A. Nurdin, Pengaruh Kedalaman Terhadap Tahanan Pentanahan Di Area Rusunawa Kampus Universitas Pgri Palembang,” J. Ampere, vol.4 no.2, p.327,2020
Published
2022-12-09
How to Cite
Seftiani, Y., & Novizon, N. (2022, December 9). Studi Kelayakan Sistem Pentanahan pada Gedung Teknik Elektro Universitas Andalas. Elektron : Jurnal Ilmiah, 14(2), 45-49. https://doi.org/https://doi.org/10.30630/eji.14.2.297
Section
Articles